Three-dimensional numerical simulation and analysis of the airside performance of slotted fin surfaces with radial strips. (English) Zbl 1191.80043

Summary: Purpose - To provide some heat transfer and friction factor results for fin-and-tube heat transfer surfaces which may be used in air conditioning industry.
Design/methodology/approach - Numerical simulation approach was adopted to compare the plain plate fin and three types of radial slotted fin surfaces.
Findings - It is found that at the same frontal velocity (1.0-3 m/s) the plain plate fin has the lowest heat transfer rate with the smallest pressure drop. The full slotted fin surface has the highest heat transfer rate with the largest pressure drop penalty. The partially slotted fin (where the strips are mainly located in the rear part of the fin) and the back slotted fin are some what in between. Under the identical pumping power constraint, the partially slotted fin surface behaves the best.
Research limitations/implications - The results are only valid the two-row fin surface.
Practical implications - The results are very useful for the design of two-row tube fin surfaces with high efficiency.
Originality/value - This paper provides original information of slotted fin surface with radial strips from the field synergy principle.

MSC:

80M12 Finite volume methods applied to problems in thermodynamics and heat transfer
80A20 Heat and mass transfer, heat flow (MSC2010)
PDFBibTeX XMLCite
Full Text: DOI Link

References:

[1] DOI: 10.1016/S0017-9310(98)00165-3 · Zbl 0925.76413 · doi:10.1016/S0017-9310(98)00165-3
[2] DOI: 10.1080/10407780152655379 · doi:10.1080/10407780152655379
[3] DOI: 10.1016/S0017-9310(97)00272-X · Zbl 0925.76667 · doi:10.1016/S0017-9310(97)00272-X
[4] DOI: 10.1016/j.ijheatfluidflow.2004.11.003 · doi:10.1016/j.ijheatfluidflow.2004.11.003
[5] DOI: 10.1115/1.2910726 · doi:10.1115/1.2910726
[6] Jing, C.M. and Ralphl, W. (2001), ”Numerical predictions of Wavy fin coil performance”,Enhanced Heat Transfer, pp. 159-73.
[7] DOI: 10.1007/BF02653243 · doi:10.1007/BF02653243
[8] DOI: 10.1016/S0017-9310(01)00081-3 · Zbl 1091.76510 · doi:10.1016/S0017-9310(01)00081-3
[9] Tao, W.Q., Guo, Z.Y. and Wang, B.X. (2002a), ”Field synergy principle for enhancing convective heat transfer its extension and numerical verifications”,International Journal of Heat and Mass Transfer, Vol. 45, pp. 849-56. · Zbl 1006.76561 · doi:10.1016/S0017-9310(02)00097-2
[10] DOI: 10.1016/S0017-9310(02)00173-4 · Zbl 1032.76688 · doi:10.1016/S0017-9310(02)00173-4
[11] Wang, S., Li, Z.X. and Guo, Z.Y. (1998), ”Novel concept and device of heat transfer augmentation”,Proceeedings of 11th International Heat Transfer Conference, Vol. 5, pp. 405-8.
[12] DOI: 10.1016/S0017-9310(01)00011-4 · doi:10.1016/S0017-9310(01)00011-4
This reference list is based on information provided by the publisher or from digital mathematics libraries. Its items are heuristically matched to zbMATH identifiers and may contain data conversion errors. In some cases that data have been complemented/enhanced by data from zbMATH Open. This attempts to reflect the references listed in the original paper as accurately as possible without claiming completeness or a perfect matching.